FIRE PUMP REPACKING
The Jesse Brown VA Medical Center in Chicago, IL, requires a repack on a Peerless 5AEF11G 1000 GPM Fire Pump in the main fire pump room of the Bed Tower as required by local fire codes and regulatory authorities to ensure the fire system functions properly in event of an emergency. Contractor shall supply all labor, tools, materials and travel to and from worksite.
Please use the attached SF1449 titled "36C25226Q0689_2 SAM.gov" to submit quotes.
Contractor shall replace the packing around the main fire pump at Jesse Brown VA Medical Center. Work includes: removing existing packing, inspecting the stuffing box/gland/shaft sleeve, cleaning the stuffing box, repacking with like or approved materials, visually inspecting the unit, manually rotating the shaft to ensure free rotation, performing work during regular business hours (7:00 a.m. – 5:00 p.m.), performing daily clean-up, and enabling pump operation with a visual inspection for leaks. All work must comply with NFPA 99, OSHA, Joint Commission, VA, UL, NEC, state and local regulations, and manufacturer standards.
We post new life safety opportunities in Illinois as agencies publish them. Get them in one email — free, and unsubscribe whenever.
"US""53214""MILWAUKEE""WI""USA""GREAT LAKES ACQUISITION CENTER""115 S 84TH ST""Wage Determination - Cook County.pdf"257578"file"".pdf""1""2026-09-02T18:46:03.656+00:00""dbe230c9912e40e09691f101c203a4f3""public""0""public""1c796e4b5dc5454aadb5cc9ddfc6684e""0"2"0""36C25226Q0689_2 SAM.gov.pdf"537793"file"".pdf""1""2026-09-02T18:46:03.656+00:00""754a3a5e422d4a9ea748ae572485adf9""public""0""public""db6ef9d81467463591ab2d22b9324bd1""0"1"0"Most Illinois work asks for the two below, and the solicitation documents are where it’s stated. Here’s what each costs through Light RFP if you need one.
Source: SAM.gov (notice 3e2670cc2f734a71a2c5f8a3d37e10b8), retrieved via the SAM.gov Get Opportunities API. View the official posting, and always confirm requirements and deadlines with the issuing agency.