SALIENT CHARACTERISTICS
for
Structural Trainer Liner
DESCRIPTION: Replace liner inside the structural trainer
REQUIREMENTS: The liner components units shall:
Designed to meet all referenced safety, thermal, and regulatory specifications, this specific material is engineered for extreme live-fire training evolutions.
Specifically formulated for Class A, B, C, D, Electrical, and F/K fires within a controlled burn cell which complies with NFPA 1402 and related standards.
Made of a cementitious high temp composite formula, which has a negative health impact when installed by certified installers.
Have Kevlar additives
Unique tongue and groove installation method
Stainless Steel mounting hardware
Have five (5) to ten (10) year warranty to replace
Able to withstand 150 psi nozzle forces
1.5 inches thick requires no additional insulation behind its barrier
Heat transfer 10.4% (1000 degree / 140 degree in 10 minutes)
Complies with all NFPA suggested burn matrix formulas
Certified as a protective skin for flammable hazmat storage cells
Source: SAM.gov (notice d5b7032a954445e4ab372345b8d13352), retrieved via the SAM.gov Get Opportunities API. View the official posting — always confirm requirements and deadlines with the issuing agency.